Data center · opened April 20, 2015
SEC1 Secaucus
615 Sedgebank Road, Secaucus, NJ 07094
- Critical IT
- 8.4 MW
- Data halls
- 71,300 sq ft
- Networks on-net
- 31
- Halls above BFE
- 6.8 ft
- Dry Floor above BFE
- 24.2 ft
SEC1 occupies a former refrigerated distribution warehouse on the Hackensack side of Secaucus, four miles west of Midtown Manhattan. We bought it in 2014 because the walls and the roof were sound and the floor was in the wrong place. The data halls sit on a new concrete deck built inside the old shell, and since 2023 Hall 4, the Dry Floor, sits on a new steel-framed level above them.
01 Flood engineering
Where the water is, and where we are
When we bought the building in 2014 its warehouse floor was at grade, 6.9 feet, and the line Hurricane Sandy had left on the loading-dock wall was 1.7 feet above it. We did not raise the building. We built a new floor inside it: a cast-in-place concrete deck on 286 new columns, with its top at 16.8 feet, and put the data halls on that. The old floor underneath is now parking, stores and the loading area, and everything on it is built to get wet.
In 2022 we raised our design flood elevation from 15.0 to 18.5 feet (see the Raise program). The halls were already built, so instead we moved what could be moved and walled in what could not. The switchgear and UPS went up to a new electrical gallery at 21.0 feet, the generators onto plinths at 20.0 feet, and the whole site is now inside a perimeter barrier of wall, berm and seven deployable gates, with its top at 19.5 feet. Hall 4, the Dry Floor, was built on top at 34.2 feet.
Section through SEC1. Vertical scale true; horizontal schematic. Water shown at the base flood elevation, 10.0 ft.
- Drawing
- CGD-SEC1-A-301
- Title
- Building section A–A
- Rev.
- F
- Date
- 2024-06-03
- Drawn
- EMC
- Checked
- TW
- Scale
- 1 in = 20 ft vert.
- Sheet
- 1 of 1
| Level | ft NAVD 88 | vs. BFE |
|---|---|---|
| Hall 4, the Dry Floor, finished floor | 34.2 | +24.2 |
| Electrical gallery (switchgear and UPS) | 21.0 | +11.0 |
| Generator plinths | 20.0 | +10.0 |
| Perimeter flood barrier, top | 19.5 | +9.5 |
| Our design flood elevation since 2022 | 18.5 | +8.5 |
| Halls 1 to 3, finished floor | 16.8 | +6.8 |
| Our design flood elevation, 2014 superseded | 15.0 | +5.0 |
| 0.2% annual chance flood | 11.8 | +1.8 |
| Base flood elevation (1% annual chance, Zone AE) | 10.0 | 0.0 |
| High-water mark, October 30, 2012Debris line on the old loading-dock wall, surveyed in 2014. | 8.6 | −1.4 |
| Site grade (average) | 6.9 | −3.1 |
02 Halls
Halls and suites
| Hall | Level | Area | Critical IT | Cabinet density | Tier | Opened |
|---|---|---|---|---|---|---|
| Hall 1 | Deck | 17,600 sq ft | 1.9 MW | 7.5 kW average, 20 kW maximum | Standard | 2015 |
| Hall 2 | Deck | 17,200 sq ft | 1.8 MW | 7.5 kW average, 20 kW maximum | Standard | 2015 |
| Hall 3 | Deck | 17,600 sq ft | 1.9 MW | 7.5 kW average, 20 kW maximum | Standard | 2017 |
| Hall 4 | Level 2 | 18,900 sq ft | 2.8 MW | 15 kW average, 45 kW with rear-door cooling | Dry Floor | 2023 |
03 Specifications
Specifications
From spec sheet SEC1-SPEC, revision H, September 30, 2026. Figures are design values unless they are dated.
Location
| Address | 615 Sedgebank Road, Secaucus, NJ 07094 |
|---|---|
| Distance | 4.3 miles west of Midtown Manhattan; 1.7 miles from Secaucus Junction station |
| Flood zone | Zone AE, base flood elevation 10.0 ft NAVD 88 |
| Halls 1 to 3 | 6.8 ft above base flood elevation, behind a barrier 9.5 ft above it |
| Hall 4 (Dry Floor) | 24.2 ft above base flood elevation |
Building
| Construction | Refrigerated warehouse (1973), rebuilt as a data center 2014 to 2015 with a new cast-in-place structural deck; Level 2 added 2022 to 2023 on a new steel frame |
|---|---|
| Gross area | 148,600 sq ft (13,805 m²) |
| Data halls | 71,300 sq ft (6,624 m²) in four halls |
| Floor loading | Halls 1 to 3: 250 lb/ft² (12.0 kN/m²); Hall 4: 200 lb/ft² (9.6 kN/m²) |
| Clear height | Halls 1 to 3: 16 ft 6 in; Hall 4: 18 ft 0 in, to the underside of structure |
| Floor | Slab, no raised floor; overhead busway and cable tray |
| Wind | Level 2 envelope and roof rated for 140 mph (3-second gust) |
| Seismic design category | B |
| Loading | Two covered dock positions with a dock lift to deck level; 10,000 lb freight elevator to Level 2 |
Power
| Utility service | Two 26.4 kV feeders from separate substations, automatic throw-over |
|---|---|
| Critical IT capacity | 8.4 MW (Halls 1 to 3: 5.6 MW; Hall 4: 2.8 MW) |
| UPS | Halls 1 to 3: block redundant, four modules to carry three; Hall 4: 2N. Lithium-ion batteries, 6 minutes at full load |
| Generators | Ten 2.25 MW diesel sets on plinths at 20.0 ft; N+1 for Halls 1 to 3, 2N for Hall 4 |
| Emissions control | Selective catalytic reduction and diesel particulate filters on every set (fitted 2025) |
| Fuel | 58,000 US gal (219,550 L) on site: 72 hours at full design load. Renewable diesel since March 2026 |
| Distribution | A and B feeds to every cabinet; 208 V three-phase standard, 415 V in Hall 4 |
| Cabinet density | Halls 1 to 3: 7.5 kW design average, 20 kW maximum; Hall 4: 15 kW average, 45 kW with rear-door heat exchangers, higher with liquid cooling by arrangement |
Cooling
| Plant | Five 900-ton water-cooled chillers (N+2) with waterside economizers |
|---|---|
| Free cooling | 3,910 hours in 2025 |
| Halls 1 to 3 | Chilled-water air handlers (N+1 per hall), hot-aisle containment |
| Hall 4 | Fan walls (N+1), hot-aisle containment, chilled-water taps for rear-door heat exchangers and coolant distribution units |
| Supply air | 64.4 to 80.6 °F (18 to 27 °C), humidity within the recommended envelope for IT equipment |
| Make-up water | Two municipal connections and 96 hours of storage for the cooling towers |
Fire and life safety
| Detection | Aspirating smoke detection in every hall and the meet-me rooms; spot detection elsewhere |
|---|---|
| Suppression | Double-interlock pre-action sprinklers in the halls; clean agent in the electrical gallery and meet-me rooms |
| Generator yard | Heat detection and water mist in every generator enclosure (fitted October 2025) |
Security
| Perimeter | 8 ft fence; crash-rated bollards and gates at both vehicle entrances |
|---|---|
| Staff | Security officers on site 24 hours a day, every day |
| Access | Card and palm-vein readers; mantraps at the building entrance and each hall; anti-passback |
| Video | Cameras on every aisle, cage door, entrance and the perimeter; recordings kept for 90 days¹ |
| Visitors | Authorized by the customer in the portal; government photo ID on arrival |
¹ A customer may ask for privacy masking inside its own cage. Requests are reviewed by the site lead, and the cage door and the aisle stay in view.
Connectivity
| Model | Carrier-neutral |
|---|---|
| Networks on-net | 31 |
| Fiber entrances | Four, in separate vaults on the north, east, south and west sides; conduits sealed to 19.5 ft |
| Meet-me rooms | MMR-A at deck level; MMR-B on Level 2 |
| Internet exchanges | Two regional exchanges, reached over Cordgrass waves |
| Cordgrass IP | Blended transit from four upstream networks, 1 to 100 Gb/s |
| To NWK1 | Two diverse dark fiber routes, 8.8 and 12.2 miles |
Operations and amenities
| On site | Critical facilities engineers and remote hands technicians, 24 hours a day |
|---|---|
| NOC | 24 hours, by telephone, the portal and email |
| Amenities | Customer lounge, two conference rooms, a build room with ESD benches, crash carts, loaner tools, lockers, showers, storage cages, Wi-Fi, parking |
04 Getting there
Getting there, and getting things delivered
- Arrival
- Visitors and customers park in the deck-level car park and enter by the main door on the north side. Bring government photo ID; your name must be on your company’s access list in the portal.
- Deliveries
- Weekdays 07:00 to 19:00 at the south dock. Outside those hours, call the NOC first. Label every package with your company name, account number and cage or cabinet.