Scheduled work ·

SEC1: acceptance test of the new perimeter flood barrier

  1. Completed

    The barrier passed its acceptance test. All seven gates deployed in 3 hours 52 minutes on this first attempt, and gates 1 and 2 held water to 19.5 ft with seepage inside the allowance.

  2. Scheduled

    The contractor will deploy all seven gates in the new SEC1 perimeter barrier for its acceptance test, and flood-test gates 1 and 2 against standing water. The south entrance will be closed for the morning.

Window

This notice affected

  • SEC1 Secaucus: Flood protection (scheduled work)
  • SEC1 Secaucus: Access and security (scheduled work)