Incident report ·

SEC1: utility outage and generator fire; Hall 2 temperatures exceeded limits

  1. Post-incident report

    Our report on this incident, PIR-2025-03, is published. It covers the cause of the fire, why the chiller shedding sequence let Hall 2 overheat, what we have changed and what we owe the customers affected.

  2. Resolved

    Both utility feeders have been stable overnight. The nine remaining generators have been inspected and load-tested this morning. We will publish a full report on this incident within thirty days.

  3. Monitoring

    Utility feeder 2 was restored at 17:46 and SEC1 transferred back to utility power at 18:20. Hall 2 has been within its normal range since 16:07. Generator 3 is isolated and will stay out of service until it has been inspected.

  4. Update

    A third chiller was restored at 15:38. Hall 2 supply air peaked at 91.4 °F at 15:42 and is now falling. Some customers in Hall 2 report equipment shutting down on high temperature. Remote hands can power equipment back on at your request; please call the NOC rather than opening a ticket.

  5. Identified

    At 15:12 a fire started in the exhaust section of generator 3. Our engineers shut the set down and put the fire out with portable extinguishers; the fire department attended and confirmed that it is out. No one was hurt. With generator 3 out of service, Halls 1 to 3 are on generator power with no spare set, and at 15:13 the generator controls shed two of the five chillers to protect the remaining sets. Supply air temperatures in Hall 2 are above the normal range. Hall 4 is not affected.

  6. Investigating

    SEC1 lost both utility feeders at 13:41 and transferred to generator power as designed. All customer loads are on generator power and normal. We are in contact with the utility, which reports wider outages in Hudson County.

Read the post-incident report

Duration

From Jun 24, 2025 · 13:41 EDT
to Jun 25, 2025 · 09:10 EDT

This incident affected

  • SEC1 Secaucus: Power (degraded performance)
  • SEC1 Secaucus: Cooling (partial outage)